High-Efficiency, Water-Cooled
Indoor Liquid Screw Chiller
R-134a Refrigerant
150 to 400 nominal tons
The 30XW units are high-efficiency, indoor water-cooled chillers with a quiet, low-vibration design featuring screw compressors. The units have excellent part load efficiency and a compact footprint less than 48 in. wide, making them great replacement units.
Options
Factory-Installed Options
- Wye-delta start
- Dual point power connection (325-400 ton)
- Non-fused disconnect
- Control power transformer
- 115-v GFCI (ground fault circuit interrupter) convenience outlet
- Marine water boxes
- Flange connections
- Suction service valves
- Isolation valves
- One-pass evaporator water box
- Three-pass evaporator water box
- 300 psi (2068 kPA) water side operating pressure rating
- One-pass condenser water box
- Minimum load control
- Navigator display module
- LON (Local Operating Network) translator control
- BACnet Communication
- EMM (Energy Management Module)
- Standard water-side operating pressure of 150 psig (1034 kPa) with an available option of 300 psig (2068 kPa)
- Discharge and liquid line shutoff valves
Field-Installed Accessories
- Temperature reset sensor
- EMM
- LON translator control
- BACnet translator control
- Sound Attenuation Packages
- Navigator display module
- Neoprene vibration isolation pads
- Vibration isolation springs
Physical Data
Size |
Capacity |
Input
power
(kW) |
Evaporator
flow |
Evaporator
pressure drop |
Condenser flow |
Condenser
pressure drop |
tons |
output (kW) |
|
gpm |
L/s |
Ft of
water |
kPa |
gpm |
L/s |
Ft of
water |
kPa |
150 |
160.0 |
562.7 |
105.0 |
384 |
24.2 |
11.1 |
33.2 |
480 |
30.3 |
14.1 |
42.1 |
175 |
170.1 |
598.2 |
110.5 |
408 |
25.8 |
12.4 |
37.1 |
510 |
32.2 |
15.8 |
47.2 |
185 |
178.2 |
626.7 |
120.1 |
428 |
27.0 |
13.6 |
40.7 |
535 |
33.7 |
17.2 |
51.4 |
200 |
191.1 |
672.1 |
123.9 |
459 |
28.9 |
15.4 |
46.0 |
573 |
36.2 |
19.5 |
58.3 |
225 |
222.5 |
782.5 |
147.7 |
534 |
33.7 |
12.0 |
35.9 |
668 |
42.1 |
12.8 |
38.3 |
250 |
241.1 |
847.9 |
151.9 |
579 |
36.5 |
13.9 |
41.5 |
723 |
45.6 |
14.9 |
44.5 |
260 |
244.8 |
861.0 |
165.7 |
588 |
37.1 |
14.3 |
42.7 |
734 |
46.3 |
15.3 |
45.7 |
275 |
262.8 |
924.3 |
168.2 |
631 |
39.8 |
16.3 |
48.7 |
788 |
49.7 |
17.4 |
52.0 |
300 |
285.5 |
1004.1 |
184.3 |
685 |
43.2 |
18.9 |
56.5 |
857 |
54.0 |
20.3 |
60.7 |
325 |
322.2 |
1133.0 |
204.7 |
773 |
48.8 |
15.6 |
46.6 |
966 |
61.0 |
10.9 |
32.6 |
350 |
343.0 |
1206.3 |
216.8 |
823 |
51.9 |
17.4 |
52.0 |
1029 |
64.9 |
12.3 |
36.8 |
375 |
364.3 |
1281.2 |
236.5 |
874 |
55.2 |
19.5 |
58.3 |
1093 |
69.0 |
13.7 |
41.0 |
400 |
385.0 |
1354.0 |
242.8 |
924 |
58.3 |
21.5 |
64.3 |
1155 |
72.9 |
15.2 |
45.4 |
Size |
Full load
efficiency
(kW/Ton) |
IPLV
(kw/Ton) |
150 |
0.656 |
0.561 |
175 |
0.650 |
0.550 |
185 |
0.674 |
0.563 |
200 |
0.648 |
0.556 |
225 |
0.664 |
0.537 |
250 |
0.630 |
0.526 |
260 |
0.677 |
0.547 |
275 |
0.640 |
0.534 |
300 |
0.646 |
0.539 |
325 |
0.636 |
0.476 |
350 |
0.632 |
0.472 |
375 |
0.649 |
0.481 |
400 |
0.631 |
0.475 |
LEGEND
AHRI = Air Conditioning, Heating and Refrigeration Institute
IPLV = Integrated Part Load Value
NOTES
1. Rated in accordance with AHRI Standard 550/590 at standard rating conditions.
2. Standard rating conditions are as follows:
Cooler Conditions:
Leaving Water Temperature: 44°F (6.7°C)
Flow: 2.4gpm per ton (0.043 L/s per kW)
Condenser Conditions:
Entering Water Temperature: 85°F (29.4°C)
Flow: 3.0gpm per ton (0.054 L/s per kW)
Fouling Factor (Cooler):
0.00010 hr x sq ft x °F per Btuh (0.000018m2 x K per W)
Fouling Factor (Condenser):
0.00025 hr x sq ft x °F per Btuh (0.000044m2 x K per W)
3. IPLV is a single number part load efficiency value calculated from using the efficiency values at 100%, 75%, 50%, and 25% of load when the chiller is operating in AHRI conditions.
4. All data in the above table was generated in Packaged Chiller Builder version 3.29. Please refer to the most current version of the Packaged Chiller Builder for the most up-to-date data.
5. Contact Carrier for custom ratings.