600 to 2,000 nominal cfm
42DC – Standard unit
42DCD – District cooling
Carrier’s 42DC Standard Cooling/ 42DCD District Cooling Chilled Water Fan Coil Units, furred-in with capacities from 600 to 2000 cfm are ideal for installations in residential, hotels, motels, apartments, offices, hospitals, schools and other multi-room buildings.
Carrier 42 series terminals require very little space and are easy to install.
Physical Data
42DC - Standard Unit (Sizes 006 - 012)
|
006 |
008 |
010 |
012 |
Nominal Airflow (cfm) |
600 |
800 |
1000 |
1200 |
NOminal Airflow (l/s) |
283 |
378 |
472 |
566 |
Fluid Cooling Capacity (Btu/hr)* |
15,076 |
22,428 |
25,365 |
33,597 |
Fluid Cooling Capacity (kW)* |
4.42 |
6.57 |
7.43 |
9.85 |
Motor Type |
Permanent Split Capacitor |
Motor Nominal Power Output (Watts) |
118 |
118 |
200 |
2×118 |
Motor Nominal Current (Amps) |
1.11 |
1.11 |
1.9 |
2×1.11 |
Fan Type |
Centrifugal Forward Curved Blades |
Sound Pressure High (dB(A))** |
40.3 |
42.0 |
48.4 |
47.2 |
Sound Pressure Medium (dB(A))** |
38.3 |
38.9 |
44.8 |
43.1 |
Sound Pressure Low (dB(A))** |
35.5 |
36.5 |
38.6 |
39.8 |
Water Flow (l/s) |
0.12 |
0.18 |
0.20 |
0.26 |
Water Pressure Drop (kPa) |
22.2 |
54.4 |
46.8 |
49.9 |
Coil (Row/FPI) |
4 / 14 |
Coil Working Pressure (Mpa) |
1.72 |
Connection In-Out (sweat) /Material |
5/8″ / Copper |
Connection Condensate Drain / Material |
7/8″ / GI Steel |
Notes:
* Base on motor at high speed, standard air and dry coil operation, 5.6°C water temperature rise; entering air temperature 24.4°C DB; 17.2°C WB, Entering water temperature 7.2°C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
42DC – Standard Unit (Sizes 014 – 020)
|
014 |
016 |
018 |
020 |
Nominal Airflow (Cfm) |
1400 |
1600 |
1800 |
2000 |
Nominal Airflow (l/s) |
661 |
755 |
852 |
943 |
Fluid Cooling Capacity (Btu/hr)* |
36,799 |
46,716 |
50,362 |
52,887 |
Fluid Cooling Capacity (kW)* |
10.79 |
13.69 |
14.76 |
15.50 |
Motor Type |
Permanent Split Capacitor |
Motor Nominal Power Output (Watts) |
300 |
450 |
450 |
450 |
Motor Nominal Current (Amps) |
2.24 |
2.89 |
2.89 |
2.89 |
Fan Type |
Centrifugal Forward Curved Blades |
Sound Pressure High (dB(A))** |
49.2 |
48.6 |
48.9 |
49.7 |
Sound Pressure Medium (dB(A))** |
46.4 |
46.9 |
47.6 |
48.1 |
Sound Pressure Low (dB(A))** |
44.6 |
44.8 |
44.7 |
45.6 |
Water Flow (l/s) |
0.29 |
0.37 |
0.40 |
0.42 |
Water Pressure Drop (kPa) |
39.0 |
50.7 |
60.2 |
54.3 |
Coil (Row/FPI) |
4 / 14 |
Coil Working Pressure (Mpa) |
1.72 |
Connection In-Out (sweat) /Material |
1″ / Copper |
Connection Condensate Drain / Material |
7/8″ / GI Steel |
Notes:
* Base on motor at high speed, standard air and dry coil operation, 5.6°C water temperature rise; entering air temperature 24.4°C DB; 17.2°C WB, Entering water temperature 7.2°C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
42DCD – District Cooling Unit (Sizes 006 – 012)
|
006 |
008 |
010 |
012 |
Nominal Airflow (Cfm) |
600 |
800 |
1000 |
1200 |
NOminal Airflow (l/s) |
283 |
378 |
472 |
566 |
Fluid Cooling Capacity (Btu/hr)* |
15,076 |
22,428 |
25,365 |
33,597 |
Fluid Cooling Capacity (kW)* |
4.42 |
6.57 |
7.43 |
9.85 |
Motor Type |
Permanent Split Capacitor |
Motor Nominal Power Output (Watts) |
118 |
118 |
200 |
2×118 |
Motor Nominal Current (Amps) |
1.11 |
1.11 |
1.9 |
2×1.11 |
Fan Type |
Centrifugal Forward Curved Blades |
Sound Pressure High (dB(A))** |
40.3 |
42.0 |
48.4 |
47.2 |
Sound Pressure Medium (dB(A))** |
38.3 |
38.9 |
44.8 |
43.1 |
Sound Pressure Low (dB(A))** |
35.5 |
36.5 |
38.6 |
39.8 |
Water Flow (l/s) |
0.12 |
0.18 |
0.20 |
0.26 |
Water Pressure Drop (kPa) |
22.2 |
54.4 |
46.8 |
49.9 |
Coil (Row/FPI) |
4 / 14 |
Coil Working Pressure (Mpa) |
1.72 |
Connection In-Out (sweat) /Material |
5/8″ / Copper |
Connection Condensate Drain / Material |
7/8″ / GI Steel |
Notes:
* Base on motor at high speed, standard air and dry coil operation, 8.9°C water temperature rise; entering air temperature 24.4°C DB; 17.2°C WB, Entering water temperature 5.5°C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
42DCD – District Cooling Unit (Sizes 014 – 020)
|
014 |
016 |
018 |
020 |
Nominal Airflow (Cfm) |
1400 |
1600 |
1800 |
2000 |
Nominal Airflow (l/s) |
661 |
755 |
852 |
943 |
Fluid Cooling Capacity (Btu/hr)* |
36,799 |
46,716 |
50,362 |
52,887 |
Fluid Cooling Capacity (kW)* |
10.79 |
13.69 |
14.76 |
15.50 |
Motor Type |
Permanent Split Capacitor |
Motor Nominal Power Output (Watts) |
300 |
450 |
450 |
450 |
Motor Nominal Current (Amps) |
2.24 |
2.89 |
2.89 |
2.89 |
Fan Type |
Centrifugal Forward Curved Blades |
Sound Pressure High (dB(A))** |
49.2 |
48.6 |
48.9 |
49.7 |
Sound Pressure Medium (dB(A))** |
46.4 |
46.9 |
47.6 |
48.1 |
Sound Pressure Low (dB(A))** |
44.6 |
44.8 |
44.7 |
45.6 |
Water Flow (l/s) |
0.29 |
0.37 |
0.40 |
0.42 |
Water Pressure Drop (kPa) |
39.0 |
50.7 |
60.2 |
54.3 |
Coil (Row/FPI) |
4 / 14 |
Coil Working Pressure (Mpa) |
1.72 |
Connection In-Out (sweat) /Material |
1″ / Copper |
Connection Condensate Drain / Material |
7/8″ / GI Steel |
Notes:
* Base on motor at high speed, standard air and dry coil operation, 8.9°C water temperature rise; entering air temperature 24.4°C DB; 17.2°C WB, Entering water temperature 5.5°C.
** Sound measurement in accordance with Standard JIS8616-2006 (1.5m below the unit bottom).
Reviews